Series STRA Duct Mounted Airflow Measurement Station
Integral Flow Straightener, Ideal for Turbulent Measuring Conditions
The Series STRA Airflow Measurement Station is easy to install -- simply connect the tubing to the station fittings, then to a differential pressure manometer, gage, transmitter or switch. Single or multiple airflow elements are factory mounted and pre-piped in a casing designed for flanged connection to the duct work. The Series STRA utilizes an airflow averaging element in a head-type device, generating a differential (velocity) pressure signal similar to the orifice, venturi, and other head producing primary elements. It has been developed with a honeycomb airflow straightening section for use in duct systems having highly turbulent conditions at the point of measurement. Strategically located sensing ports continually sample the total and static pressures when inserted normal to flow. Total pressures sensed by the upstream ports are continually averaged within the airflow element in an isolated chamber. The static sensing ports are averaged in a second isolation chamber. Multiple elements are joined together for connection to a differential measurement device (gage, transmitter, etc.) for flow measurement and indication purposes.
Models & Ordering
Specifications
- Accuracy:
- Within 2% of actual flow when installed in accordance with published recommendations.
- K Factor:
- 0.97.
- Velocity Range:
- 100 to 10,000 fpm (0.51 to 51 m/s).
- Wetted Materials:
- Elements: 6063-T5 anodized aluminum; Casings: 16 ga G90 galvanized steel, 3003 aluminum air flow straightener.
- Coatings:
- Herewith VRL 500 phenolic coating Imron 333 polyurethane enamel.
- Temperature Limits:
- Galvanized Casings and Aluminum Elements 350°F (177°C) continuous operation (in air), 400°F (204°C) intermittent operation (in air).
- Humidity Limits:
- All Airflow Stations 0 to 100% non condensing.
- Process Connections:
- 1/4" compression fittings.
Features
- Low signal-to-noise ratio.
- Honeycomb airflow straightening section with 1/2" opening by 3" depth.
- Multiple total and static pressure sensing ports along the length of the element.
- Factory mounted and pre-piped in a flanged duct section (casing).
- ±2% accuracy throughout velocity ranges of 100 fpm and over.
- Standard construction includes galvanized casing and 6063-T5 anodized aluminum flow sensors.
- Standard airflow stations can be operated (in air) continuously in temperatures up to 350°F or intermittently in temperatures up to 400°F.
- All airflow stations can be operated in humidity ranges of 0 to 100%.
- Standard airflow stations have good salt air resistance and are suitable for most HVAC applications.
- Great for use where turbulent conditions exist.
Options
- IM - Internal Pressure Connections.
- F - (Oval Stations Only).
Model Chart
Rectangular or Oval Models:EXAMPLE | STRA | O | 12 | X16 | IM | Series STRA-R12X16-IM Duct Mounted Airflow Measurement Station, 12" x 16" oval duct, with internal pressure connections. |
SERIES | STRA | Duct Mounted Airflow Measurement Station | ||||
CONFIGURATION | O R |
Oval Rectangular |
||||
DUCT HEIGHT | 8 10 12 14 15 16 18 20 22 24 26 28 30 32 34 36 37 40 44 48 52 56 60 66 72 78 84 90 96 102 108 114 120 200MM 250MM 300MM 350MM 370MM 400MM 425MM 450MM 500MM 550MM 565MM 600MM 610MM 615MM 700MM 750MM 765MM 1000MM 1100MM 1200MM 1250MM 1300MM 1450MM |
8" 10" 12" 14" 15" 16" 18" 20" 22" 24" 26" 28" 30" 32" 34" 36" 37" 40" 44" 48" 52" 56" 60" 66" 72" 78" 84" 90" 96" 102" 108" 114" 120" 200MM 250MM 300MM 350MM 370MM 400MM 425MM 450MM 500MM 550MM 565MM 600MM 610MM 615MM 700MM 750MM 765MM 1000MM 1100MM 1200MM 1250MM 1300MM 1450MM |
||||
DUCT WIDTH | X8 X10 X12 X14 X15 X16 X18 X20 X21 X22 X24 X26 X28 X30 X32 X34 X35 X36 X39 X40 X42 X44 X48 X50 X52 X56 X60 X63 X66 X68 X72 X78 X84 X90 X96 X102 X108 X114 X120 X250MM X350MM X400MM X450MM X500MM X550MM X600MM X610MM X615MM X675MM X750MM X770MM X900MM X950MM X955MM X1000MM X1100MM X1150MM X1200MM X1370MM X1380MM X1400MM X1450MM X1470MM X1600MM X2400MM |
8" 10" 12" 14" 15" 16" 18" 20" 21" 22" 24" 26" 28" 30" 32" 34" 35" 36" 39" 40" 42" 44" 48" 50" 52" 56" 60" 63" 66" 68" 72" 78" 84" 90" 96" 102" 108" 114" 120" 250MM 350MM 400MM 450MM 500MM 550MM 600MM 610MM 615MM 675MM 750MM 770MM 900MM 950MM 955MM 1000MM 1100MM 1150MM 1200MM 1370MM 1380MM 1400MM 1450MM 1470MM 1600MM 2400MM |
||||
OPTIONS | F IM |
1-1/2" Flange for Oval Mount Station Only Internal Pressure Connections |
Circular Models:
EXAMPLE | STRA | C | 12 | Series STRA-C12 Duct Mounted Airflow Measurement Station, 12" diameter duct. |
SERIES | STRA | Duct Mounted Airflow Measurement Station | ||
CONFIGURATION | C | Circular | ||
DUCT DIAMETER | 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 40 41.5 42 44 48 54 56 60 66 72 78 84 90 96 102 108 114 120 |
8" 10" 12" 14" 16" 18" 20" 22" 24" 26" 28" 30" 32" 34" 36" 40" 41.5" 42" 44" 48" 54" 56" 60" 66" 72" 78" 84" 90" 96" 102" 108" 114" 120" |
Drawings