Series 16G, 8G, 4G Temperature/Process Loop Controllers
Universal Input, Dual Output, On/Off PID or FUZZY Logic Output Control
The Series 16G, 8G, AND 4G Temperature/Process Loop Controllers allow for monitoring and control of temperature or process conditions. The controller features two independent control outputs for dual loop control using on/off, auto-tune or self-tune PID, fuzzy logic, or manual control methods. RS-485 interface is included with Modbus® communication protocol, for easy bench-top configuration or integration with a PLC or data control system.
Product Applications
- Oven control
- Packaging equipment
- Parts washers
Models & Ordering
Specifications
- Inputs:
- Thermocouple, RTD, DC voltages or DC current.
- Display:
- Process value: 4 digit, 0.47" H (12mm), orange LCD; Set point value: 4 digit, 0.47" H (12mm), green LCD.
- Accuracy:
- ± 1.8°F plus ±0.3% of span (±1°C plus ±0.3% of span) at 77°F (25°C) after 20 minutes warm up.
- Power Requirements:
- 100 to 240 VAC -20/+8%, 50/60 Hz; Optional 24 VDC, ±10%.
- Power Consumption:
- 5 VA max.
- Operating Temperature:
- 32 to 122°F (0 to 50°C).
- Storage Temperature:
- -42 to 150°F (-20 to 65°C).
- Memory Backup:
- Nonvolatile memory.
- Control Output Ratings:
- Relay: SPST, 5 A @ 250 VAC resistive; Voltage pulse: 12 V (max. 40 mA); Current: 4 to 20 mA; Linear voltage: 0 to 10 V.
- Alarm Relay Ratings:
- 3 A @ 250 VAC resistive.
- Communication:
- RS-485 Modbus® ASCII/RTU communication protocol.
- Weight:
- 9 oz (255g).
- Front Panel Rating:
- IP66.
- Agency Approvals:
- CE, cULus.
Features
- On/off, PID, fuzzy logic, or manual output control
- Constant, sloped, program (ramp/soak), or remote set-point control
- 2 primary control outputs, 2 secondary/alarm relay outputs, and RS-485 standard on all models
- Remote set-point, input retransmission, or event input functions available with optional hardware
Accessories
Model Number | Description | Usually Ships* | Price | Order | |
---|---|---|---|---|---|
![]() |
A-600 | R/C snubber (recommended for inductive loads like a solenoid or contactor). | 1-2 Weeks | $23.25 | Order |
![]() |
A-900 | Weatherproof enclosure, type 4X, control direct panel mounts in the front of the enclosure. | Call for Details | $182.00 | Order |
![]() |
A-901 | Weatherproof enclosure, type 4X, clear plastic window with rear panel for mounting the control inside the enclosure. | Call for Details | $338.00 | Order |
![]() |
MN-1 | Mini-Node™ RS-485 to USB converter. | Call for Details | $102.00 | Order |
A-TC-K100-FB | K type, 100' on spool, fiber glass insulation, 450°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $82.00 | Order | |
A-TC-K100-FEP | K type, 100' on spool, FEP insulation, 200°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $71.00 | Order | |
A-TC-K25-FB | K type, 25' on spool, fiber glass insulation, 450°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $30.50 | Order | |
A-TC-K25-FEP | K type, 25' on spool, FEP insulation, 200°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $28.25 | Order | |
A-TC-K50-FB | K type, 50' on spool, fiber glass insulation, 450°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $48.50 | Order | |
A-TC-K50-FEP | K type, 50' on spool, FEP insulation, 200°C, yellow outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $41.75 | Order | |
A-TC-J100-FB | J type, 100' on spool, fiber glass insulation, 450°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $50.50 | Order | |
A-TC-J100-FEP | J type, 100’ on spool, FEP insulation, 200°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $38.25 | Order | |
A-TC-J25-FB | J type, 25' on spool, fiber glass insulation, 450°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $23.25 | Order | |
A-TC-J25-FEP | J type, 25' on spool, FEP insulation, 200°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $19.50 | Order | |
A-TC-J50-FB | J type, 50' on spool, fiber glass insulation, 450°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $32.25 | Order | |
A-TC-J50-FEP | J type, 50’ on spool, FEP insulation, 200°C, black outer sheath, 24 AWG, 0.20 SQMM | 1-2 Weeks | $25.50 | Order |
Videos
Product Literature
Manuals
Catalog Pages
Product Data Sheet
Approvals
Software
Drawings
Questions
- Question
- I have a Love 16B-33-LV temp controller that came with a DC01 jumper. Can you tell me what this jumper is for?
- Answer
- The jumper is used when you are using a current input (4-20 mA) signal into the controller. If you are using an RTD or thermocouple probe you do not need this jumper.
- Question
- Muffle furnace with Love 16B controller is displaying "no cont" on start up. I replaced the thermocouple but still get the same error. Any other cause for this code?
- Answer
- Did you check the INPT setting in the initial setup menu to make sure it matches the thermocouple type that you are using?
Photo Downloads
You must be logged in to view this content.Click here to login to your account.
Product Reviews
Only registered users can write reviews. Please Sign in or create an account