Series TABKIT Test, Adjust, and Balance Kit

A Complete Balancing Technician Solution

The Series TABKIT Test, Adjust, and Balance Kit combines all essential air, water, temperature, humidity, and electrical test instruments are included in this kit, creating the ultimate air and water balancing solution. The Series TABKIT has everything a balancing technician needs in a single case. A certificate of NIST calibration is included for each instrument inside the kit, ensuring accurate, durable, repeatable, and reliable measurements every time. When the products need to be recalibrated, save time by sending everything back to Dwyer. Our lab is able to service all equipment within the kit, and ensure they’re as accurate as the day you originally received them.


Complete Kit Includes:

  • Model 160G Averaging Air Flow Grid
  • Model DP3 Bluetooth-Enabled Wireless Differential Pressure Module
  • Model AP3 Bluetooth-Enabled Wireless Thermo-Anemometer Probe
  • Model RP3 Bluetooth-Enabled Wireless Thermo-Hygrometer Probe
  • Model VP3 Bluetooth-Enabled Wireless 100 mm Vane Thermo-Anemometer Probe
  • Model TAC-L Portable Digital Tachometer
  • Model CM-1 Digital Clamp Meter
  • Series 490W Wireless Hydronic Differential Pressure Manometer
  • Model 160F 18" Straight Stainless Steel Pitot Tube
  • Model 160-18 18" Stainless Steel Pitot Tube
  • Two Model A-303 Static Pressure Tips with Magnetic Mounting
  • Cooper-Atkins Model TM99A Thermistor Temperature Instrument
  • Cooper-Atkins Model 1075 General Purpose Puncture Probe
  • Hard Case


California Residents:  Click Here for Proposition 65 WARNING.

Product Applications

  • Building balancing
  • Building commissioning
  • Testing HVAC equipment performance

Models & Ordering

Shipping Information

All shipping times are dependent on product availability at time of shipment.

Although we make every effort to ensure a continuous supply of our products, occasional circumstances may force us to temporarily run out of a product, or have shipping delays. Should this occur, customers will be notified soon after placement of any orders for such products and, if applicable, items will be put on backorder. For orders requiring expedited shipment, our customer service team can be contacted to confirm product availability

Model Description Usually Ships* Price Order
TABKIT-NIST
Ships: 2-3 Weeks
Price: $7,865.00
Complete NIST calibrated Test, Adjust and Balance Kit with a hard carrying case. 2-3 Weeks* $7,865.00 Order

Specifications

AIR
Series DP3
Accuracy*:
±0.5% FS span @ 25°C (includes non linearity, hysteresis, and non repeatability).
Pressure Limits:
±10 in w.c. (±2.5 kPa).
Temperature Limits:
Operating: -4 to 140°F (-20 to 60°C); Storage: -40 to 185°F (-40 to 85°C).
Model AP3
Range:
Air velocity: 45 to 6000 FPM (0 to 30 m/s); Volumetric air: 999,999 in selected flow units; Temperature: -20 to 212°F (-29 to 100°C).
Accuracy:
Air velocity*: ±3% FS within temperature range of 40 to 90°F (4 to 32°C) -TAB option: 50 to 3900 FPM (0.25 to 20 m/s); Temperature: ±0.5°F (±0.28°C).
Model VP3
Range:
Air velocity: 40 to 5000 FPM (0.2 to 25 m/s); Volumetric air: 999,999 in selected flow units; Temperature: -20 to 212°F (-29 to 100°C); Relative humidity: 0 to 100% RH.
Accuracy:
Air velocity*: 100 to 3900 FPM: ±5% of reading ±7 FPM (0.5 to 20 m/s: ±5% of reading ±0.04 m/s); Temperature: ±0.9°F @ 77°F (±0.5°C @ 25°C); Relative humidity: ±2% @ 77°F (25°C) (10 to 90% RH); ±4% (0 to 10% RH and 90 to 100% non-condensing).
Resolution:
1 FPM (0.001 m/s).
TEMPERATURE
TM99A and 1075
Range:
0 to 200°F (-20 to 100°C).
Accuracy*:
±0.5% of reading + 2.0°F (±0.5% of reading + 1.0°C).
Resolution:
0.1°F (0.1°C).
HUMIDITY
Model RP3
Range:
RH: 0 to 100% (noncondensing); Temperature: -22 to 140°F (-30 to 60°C).
Accuracy:
RH*: ±2% @ 25°C (10 to 90% RH); ±4% (0 to 10, 90 to 100% RH); Temperature: ±0.9°F @ 77°F (±0.5°C @ 25°C).
ELECTRICAL
Model CM-1
AC Voltage:
0.1-600 V ± (1.0% + 5 dgt).
DC Voltage:
0.1-600 V ± (1.0% + 3 dgt).
AC Current:
0.1-400 A ± (2.0% + 10 dgt).
Resistance:
0.1-400 Ω ± (1.0% + 5 dgt).
ROTATION
Model TAC-L
Range:
Non-contact (RPM): 2.5 to 99,999 RPM; Contact (RPM): 0.5 to 19,999 RPM; Surface speed (m/min): 0.05 to 19,999 m/min.
Resolution:
Non-contact* (RPM): 0.1 RPM (2.5 to 999.9 RPM), 1 RPM (1000 to 19,000 RPM); Surface speed (m/min): 0.01 m/min (0.05 to 99.99 m/min), 0.1 m/ min (100.0 to 1999.9 m/min).
HYDRONIC
A-490W-6
Range:
0.4 to 200 psi, 3 to 1400 kPa.
0.4 to 75 psi, 3 to 500 kPa.
Accuracy:
2% of reading ±1 psi, 2% of reading ±7 kPa.
2% of reading ±0.5 psi, 2% of reading ±3.5 kPa.
Resolution:
0.1 psi, 1.0 kPa.
0.01 psi, 0.1 kPa.
*NIST calibrated.

Features

  • Everything a balancing technician needs in a single case
  • Best in class low flow velocity readings
  • Repeatable measurements